Function library
Monitorings
9.3.3 Monitoring functions
9-225
L
EDSVS9332S-D11 EN 3.0
9.3.3.3 External error EEr
Purpose
Process monitoring
MONIT
DCTRL--TRIP
MONIT--EEr
C0884/3
C0871
Fig. 9-174 External error EEr
Signal
Source Note
Name Type DIS DIS format CFG List Lenze
DCTRL-TRIP d C0884/3 bin C0871 2 54 -
MONIT-EEr d - - - - - -
Function
The signal EEr is obtained from the signal at the input DCTRL-TRIP-SET (level evaluation). With
default setting, this signal is obtained from terminal X5/E4 . Here, external encoders can be
connected which control the controller in the desired direction.
Any other binary signal source can also be used.
Features:
z LECOM no.: 91, 1091, 2091
z Reaction: TRIP, MESSAGE, WARNING or OFF