Function library
Code table
9-264
l
EDSVS9332S-D12 EN 3.0
Code ImportantPossible settings
No. SelectionLenzeLCD
C0265 MPOT1 INIT 0 0
1
2
Value during mains failure
lower limit of C0261
0%
MPOT1
Initialisation. Value which is accepted during
mains switching and activated motor
potentiometer.
[C0267] → Selection list 2
Digital inputs motor potentiometers
1 UP 1000 FIXED0
C0267/1: Mpot-UP
2 DOWN 1000 FIXED0
C0267/2: MPOT-Down
[C0268] MPOT1-INACT 1000 FIXED0 → Selection list 2 MPOT1
Input signal configuration
C0269
1 (C0267/1)
2 (C0267/2)
3 (C0268)
C0291 SSC override 0 0 {1 rpm} 16000 SSC override frequency
C0292 SSC IM SET 0.00 0.00 {0.01 A} 500.00 SSC Im setpoint
Motor current. Set approx. 1.0 to 1.1- fold rated
motor current for sensorless control. Setpoint
C0293 SSC dynamic 0.00 {0.01 %} 199.00 SSC Dynamic constant
C0294 VP FRQ CTRL → 0.0 {0.1 } 99.9 SSC V
p
frequency controller
Proportional gain of frequency controller
→ depending on C0086
C0295 TN FRQ CTRL → 2 {1 ms} 20000 Tn frequency controller
Adjustment time frequency controller
→ depending on C0086
C0296 DYNAMIC CONST 100 0 {0.1 } 32767 Dynamic constant
C0325 VP2 ADAPT 1.0 0.1 {0.1 } 500.0 PCTRL
Process controller adaptation gain (V
p2
)
C0326 VP3 ADAPT 1.0 0.1 {0.1 } 500.0 PCTRL
Process controller adaptation gain (V
p3
)
C0327 SET2 ADAPT 100.00 0.00 {0.01 %} 100.00 PCTRL
Set speed threshold nset2 of the process
controller adaptation (condition:
C0327 > C0328)
C0328 SET1 ADAPT 0.00 0.00 {0.01 %} 100.00 PCTRL
Set speed threshold nset1 of the process
controller adaptation (condition:
C0328 < C0327)
C0329 ADAPT ON/OFF 0 0
1
2
3
No process controller adaptation
External via input
Adaptation via setpoint
Adaptation via control difference
PCTRL
Activate process controller adaptation
C0332 PCTRL T IR 0.000 0.000 {0.001 s} 999.900 PCTRL
Acceleration time Tir
Refers to setpoint change 0...100 %
C0333 PCTRL T IF 0.000 0.000 {0.001 s} 999.900 PCTRL
Deceleration time Tif
Refers to setpoint change 0...100 %
C0336 ACT VP 0.0 {0.1 } 500.0 PCTRL
Current Vp
C0337 BI/UNIPOLAR 0 0
1
Bipolar
Unipolar
PCTRL
Bipolar/unipolar range of action
C0338 ARIT1 FUNCT 1 0
1
2
3
4
5
OUT = IN1
OUT = IN1 + IN2
OUT = IN1 - IN2
OUT = IN1 * IN2
OUT = IN1 / IN2
OUT = IN1/(100% - IN2)
ARIT1
Function selection