DLP-536: Detailed Level Procedure 363-206-285
Page 4 of 4 Issue 2, February 2000
DDM-2000 OC-3 MULTIPLEXER
14.
!
DANGER:
A high discharge current is present at connector head if
TESTING
indicator is lighted. Batteries must not be connected or disconnected
when
TESTING
indicator is lighted.
Depress test set STOP button. Proceed to Step 17.
Response: STOP indicator on test set lights
15. After 15 minutes, the test set COMPLETE indicator lights.
16. Is any REPLACE indicator on test set lighted?
If YES, then continue with Step 17.
If NO, then STOP. YOU HAVE COMPLETED THIS PROCEDURE.
17. Unplug and set aside all defective batteries.
18. Install and connect replacement batteries to battery shelf. Reconnect any
remaining good batteries to battery shelf.
19. Place batteries on high charge by depressing HIGH RATE CHG ACTIVATE
pushbutton on BATTERY CHARGER and repeat from Step 6.