A - 2 VM600 networking manual MAVM600-NET/E
Edition 9 - February 2018
APPENDIX A: MPC4 MODBUS REGISTER DEFINITIONS
Table A-1: MPC4 register definitions
Read coil or discrete input registers (Modbus function codes 01 and 02)
Rack
slot
number
(Snum)
Address
offset
(Aoff)
Channel
Internal value
type
Value
description
Modbus
starting
address
(MSA)
Value
Type
CPUM
<71
From
3 to 14
0
Channel 1, output 1
Value
Point is defined
Bit
1 Alarm+
2Alarm
3 Danger+
4 Danger
5 Sensor OK
8
Channel 1, output 2
Point is defined
9 Alarm+
10 Alarm
11 Danger+
12 Danger
13 Sensor OK
16
Channel 2, output 1
Point is defined
17 Alarm+
18 Alarm
19 Danger+
20 Danger
21 Sensor OK
24
Channel 2, output 2
Point is defined
25 Alarm+
26 Alarm
27 Danger+
28 Danger
29 Sensor OK
32
Channel 3, output 1
Point is defined
33 Alarm+
34 Alarm
35 Danger+
36 Danger
37 Sensor OK
40
Channel 3, output 2
Point is defined
41 Alarm+
42 Alarm
43 Danger+
44 Danger
45 Sensor OK
( ( slot 3 ) * 96 ) + Aoff
Same behaviour

Table of Contents

Other manuals for Meggitt VM600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Meggitt VM600 and is the answer not in the manual?

Meggitt VM600 Specifications

General IconGeneral
BrandMeggitt
ModelVM600
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals