7.3 Online Module Change Procedure
7.3.6 When user range setting is used and initial setting was made with sequence program (other system is
7
ONLINE MODULE CHANGE
(b) Click the "Execution" button to enable a module change.
If the following error window appears, the user range cannot be saved.
Click the [OK] button, dismount the module as-is, and perform the operation in
Section (2) (c) and later.
(c) After confirming that the "RUN" LED of the module has turned off, remove the
connector and dismount the module.
Always dismount the module. If mounting confirmation is made without the
module being dismounted, the module will not start properly and the "RUN" LED
will not be lit.