8 Settings via the MICT
Rev. 03/2019 121
Column: Min. Spark Duration
Minimum spark duration of the outputs
Column: Energy Output
Current energy release of the output
Columns: Misfire
Status display for the different types of misfires (primary, secondary, open, short circuit). In
case of misfire, the respective status display turns red, otherwise it is gray. With a yellow
status display misfires have occurred since the last reset of the counter.
If you hold the pointer over the status display, an overview of the misfire counter of the
respective output is displayed for all types of misfires. A maximum up to 255 is counted per
type of misfire. The counter manually resets using the menu item Device-> Send command ->
Reset misfire counters. When starting the engine and starting the self test the counters are
automatically reset.
You have the following options:
Relative/Absolute
Select via the option, whether the firing angle should be displayed absolute or relative.