8 Settings via the MICT
134 Rev. 03/2019
Warning Description
Speed (x RPM) exceeded
overspeed limit (y RPM). Previous
speed was z RPM.
Speed (x RPM) exceeded overspeed limit (
RPM).
Previous speed was z RPM (see Engine – Pickups on page
96). The reason for this may also be an interference
coupling on the trigger signal.
Temperature of device (x °
)
exceeded limit (y °C)
The temperature of the device (x °
) exceeded warning
threshold limit (y °C) for more than two minutes. Ensure
that there is sufficient air circulation and/or cooling.
8.12.6.3 Alarms
Alarms can be defined in the configuration. When doing so, each alarm is assigned a number
(see Inputs/Outputs – Alarms on page 106).
Alarm Description
Alarm number "description"
acknowledged.
The alarm number "description" was acknowledged.
Alarm number "description"
triggered.
The alarm number "description" was triggered.
All alarms reset. All alarms reset.
8.12.6.4 Failure
All system or operating errors cause the engine to be shut down.
Error Description
Alarm shutdown caused by alarm
number.
The engine was shut down by alarm number. This
function was defined in the configuration (see Inputs/
Outputs – Alarms on page 106).
Assertion failed (x). An assertion was not adhered to (x). For example, an
assumption for a value was not fulfilled in the firmware. If
the error occurs again after restarting the device, please
contact MOTORTECH.
Critical error x (y). Critical error x (y). If the error occurs again after restarting
the device, please contact MOTORTECH.
Current sensor of output bank
name failed.
The current sensor of output bank name failed. Restart
the ignition controller. If the error occurs again after
restarting the device, please contact MOTORTECH.