10 Fault elimination
Maschinenfabrik Reinhausen GmbH 2020362 6385142/08 ENETOS
®
ED
Characteristics/details Cause Remedy
Plan DSI replacement
▪ Event No. 1149
The limit value for planning mainte-
nance has been reached.
Plan maintenance and carry out maintenance
work soon, and then confirm this in the visual-
ization.
Maintenance work has been car-
ried out but not confirmed in the vi-
sualization.
Confirm maintenance work in the visualization.
Visualization operations counter
offset.
Compare visualization operations counter with
the motor-drive unit operations counter and
correct if necessary.
Maintenance data incorrect Call up the maintenance log and check the
date of the last maintenance work.
Selector maintenance is required
▪ Event No. 1152
The limit value for maintenance
has been reached.
Carry out maintenance work and then confirm
this in the visualization.
Maintenance work has been car-
ried out but not confirmed in the vi-
sualization.
Confirm maintenance work in the visualization.
Visualization operations counter
offset.
Compare visualization operations counter with
the motor-drive unit operations counter and
correct if necessary.
Maintenance data incorrect Call up the maintenance log and check the
date of the last maintenance work.
Plan selector maintenance
▪ Event No. 1151
The limit value for planning mainte-
nance has been reached.
Plan maintenance and carry out maintenance
work soon, and then confirm this in the visual-
ization.
Maintenance work has been car-
ried out but not confirmed in the vi-
sualization.
Confirm maintenance work in the visualization.
Visualization operations counter
offset.
Compare visualization operations counter with
the motor-drive unit operations counter and
correct if necessary.
Maintenance data incorrect Call up the maintenance log and check the
date of the last maintenance work.
Oil filter replacement is required
▪ Event No. 1166
The limit value for maintenance
has been reached.
▪ Signal at X1:105 and 1000 tap-
change operations made
Carry out maintenance work and then confirm
this in the visualization.
Maintenance work has been car-
ried out but not confirmed in the vi-
sualization.
Confirm maintenance work in the visualization.
Wiring error Check the wiring of terminals X1:105/106.