10 Fault elimination
Maschinenfabrik Reinhausen GmbH 2020362 6385142/08 ENETOS
®
ED
Characteristics/details Cause Remedy
Plan DSI replacement
Event No. 1149
The limit value for planning mainte-
nance has been reached.
Plan maintenance and carry out maintenance
work soon, and then confirm this in the visual-
ization.
Maintenance work has been car-
ried out but not confirmed in the vi-
sualization.
Confirm maintenance work in the visualization.
Visualization operations counter
offset.
Compare visualization operations counter with
the motor-drive unit operations counter and
correct if necessary.
Maintenance data incorrect Call up the maintenance log and check the
date of the last maintenance work.
Selector maintenance is required
Event No. 1152
The limit value for maintenance
has been reached.
Carry out maintenance work and then confirm
this in the visualization.
Maintenance work has been car-
ried out but not confirmed in the vi-
sualization.
Confirm maintenance work in the visualization.
Visualization operations counter
offset.
Compare visualization operations counter with
the motor-drive unit operations counter and
correct if necessary.
Maintenance data incorrect Call up the maintenance log and check the
date of the last maintenance work.
Plan selector maintenance
Event No. 1151
The limit value for planning mainte-
nance has been reached.
Plan maintenance and carry out maintenance
work soon, and then confirm this in the visual-
ization.
Maintenance work has been car-
ried out but not confirmed in the vi-
sualization.
Confirm maintenance work in the visualization.
Visualization operations counter
offset.
Compare visualization operations counter with
the motor-drive unit operations counter and
correct if necessary.
Maintenance data incorrect Call up the maintenance log and check the
date of the last maintenance work.
Oil filter replacement is required
Event No. 1166
The limit value for maintenance
has been reached.
Signal at X1:105 and 1000 tap-
change operations made
Carry out maintenance work and then confirm
this in the visualization.
Maintenance work has been car-
ried out but not confirmed in the vi-
sualization.
Confirm maintenance work in the visualization.
Wiring error Check the wiring of terminals X1:105/106.