Operating Parameters
B-14
P/N 7135268B
E 2008 Nordson Corporation
PURBlue EC
Output Setup
Standard Outputs
All contacts are open when the melter is switched off.
40 42 Outputs 1, 2 and 3
Description:
Determines the function of the output.
Value:
0 = Output disabled
1 = Ready
2 = Ready and pump running
3 = Fault
4 = Tank low level (only when melter has level scan feature)
5 = Service LED on
6 = Alarm
Resolution:
1
Default:
Output 1 = 1
Output 2 = 3
Output 3 = 4
Format:
Use:
Refer to Installation for information about setting up the outputs.
Control options 1, 2, 4 and 5: When the state occurs, the contact closes.
Control option 3: The contact opens when a fault occurs.
When control options 6, Alarm, is selected, the output is active whenever the
melter enters the two minute fault monitoring period. If the potential fault
condition clears before the end of the two minute period, the output signal ends.
If control option 3 and 6 are both used, the illuminated fault LED indicates a
fault signal as well as an alarm signal.
Original state: Output 1 = 1
Original state: Output 2 = 0
Original state: Output 3 = 0