Troubleshooting
6‐5
P/N 213828_11
2014 Nordson Corporation
VersaBlue_PPA
Alarm no. RedYellowGreenStatus
2 Temperature controller failure
Refer to I/O Board Failure
Pressure sensor failure
Controller fault
Controller or controller CAN module defective
Controller not connected to CAN bus
Overload
Motor short-circuit
Gateway failure
Contact fault in voltage supply or fuses have activ
ated
Gateway defective or not connected to the serial
Subnet
Serial cable IPC to gateway Subnet defective
Bus terminating resistor missing or defective
13 Temperature controller: incorrect software version
The firmware version of the controller installed is not
compatible with the IPC program version
20 Channel: Overtemperature shutdown
30 Motor phase missing
32 Motor coupling blocked or phase missing
(motor current exceeds limit)
Pump blocked by foreign material
Pump operates too sluggish
Material too cold
33 Controller: Faulty parameter file
34 Controller: No parameter file
36 Controller: Wrong type
Hardware does not correspond to software config
uration
50 Incompatible IPC software version / memory board
An attempt is being made to operate an IPC II with a
software version 6.00.000 or higher.