3
2
1
I/O
Fig. 7‐30
Inside of electrical cabinet door
Fig. 7‐31
Dial
Repair
7‐21
P/N 213828_11
2014 Nordson Corporation
VersaBlue_PPA
Replacing I/O Board, Temperature Control Board
NOTE: Switch / DIP switch settings, bus terminating resistors yes/no and
jumper settings are to be assumed from the replaced board.
The CAN address is set on the dials using a screwdriver.
I/O Board
CAN bus plug X16
Setting CAN Address
Dial (default) Board no.
SW1 SW2
0 5 1
NOTE: Dial setting SW1 may not be changed.
Temperature Control Board
CAN bus plug X9
Setting CAN Address
Dial (default) Board no. Temperature channel
S1 S2
7 1 1 1 to 6
7 2 2 7 to 12
7 3 3 13 to 18
NOTE: Dial setting S1 may not be changed.