Control panel AND standard
I/O
Operation
4‐8
P/N 213828_11
2014 Nordson Corporation
VersaBlue_PPA
Initial Startup (contd.)
Temperature setpoints (= processing temperatures)
Refer to Control Panel - Overview - / T1.
Undertemperatures / overtemperatures
Refer to Control Panel - Overview - / T2.
Activate/deactivate channels
Rename temperature channels if necessary
NOTE: Texts that the customer can change are not translated into
the selected local language.
Refer to Control Panel - Overview - / T3.
Pump speed(s) in manual mode
NOTE: To prevent excessive wear, the motor/pump speed should
not continuously fall below 5 min
‐1
(rpm) or continuously exceed
80 min
‐1
(rpm).
Refer to Control Panel - Overview - / M1.
If the motors are to be switched via the interface Standard I/O,
change the motor enable from Control panel to Control panel AND
standard I/O.
Refer to Control Panel - Overview - / M2
Standard I/O: Observe for Edge-controlled Signals
(Example)
If standby is switched on via the interface (rising edge), it can be
switched off with the seven-day clock or by the operator on the
control panel (Who-touched-me-last).
If standby is then to be switched on again via the interface, it must first
be switched off (falling edge) then on again via the interface.