Troubleshooting
6‐12
P/N 213828_11
2014 Nordson Corporation
VersaBlue_PPA
Temperature Sensor - Fault -
Every temperature sensor is monitored.
Short-circuit-triggered
The temperature is lower than - 10°C (14°F) for more than 5 seconds.
Triggered by Broken Sensor or Open Sensor Input
The temperature is lower than 305°C (581°F) for more than 5 seconds.
Automatic Reset
After the fixed internal value has been exceeded or fallen below for longer
than 5 seconds or after a defective sensor has been replaced.
Level (Variable Measuring Points)
Warning Tank Overfilled
The warning is triggered as soon as the level has reached or exceeded 98%
for longer than 5 seconds. This is a fixed internal value.
Automatic Reset
When the level falls below 90 %.
Warning Tank Level Low
As soon as the level has fallen below the set value for longer than 5 seconds,
a warning is triggered. The value for this warning is set in the screen Level
(Refer to Operation / Control Panel - Overview - / V13).
Automatic Reset
When the set value is exceeded.
Fault Tank Empty
The fault is triggered as soon as the level reaches or falls below 2 % for
longer than 5 seconds. This is a fixed internal value.
Automatic Reset
When the level exceeds 5 %.