CT Analyzer User Manual
184 OMICRON
905.xxx Error [905.xxx] Over-temperature of power supply, wait until device has cooled down.
Reason: Secondary side power supply has reached the warning temperature limit and entered save
mode to cool down.
Solution: When this error is acknowledged as long it is active, the popup window is closed and only
the message in the status line remains active until the overtemperature disappears. If the
error is not acknowledged, the popup window remains active.
Comment: The status line displays the flashing message "905.xxx Overtemp.".
Safety action: All measurements are stopped and the error message is displayed in the status line and a
popup window. After acknowledgement, the software waits at least 1 minute before the test
can be started again.
906.xxx Error [906.xxx] Excess temperature of power supply, wait until device has cooled down.
Reason: The primary side power supply has reached its warning temperature limit and entered save
mode to cool down.
Solution: When this error is acknowledged as long it is active, the popup window is closed and only
the message in the status line remains active until the overtemperature disappears. If the
error is not acknowledged, the popup window remains active.
Comment: The status line displays the flashing message "906.xxx Overtemp.".
Safety action: All measurements are stopped and the error message is displayed in the status line and a
popup window. After acknowledgement, the software waits at least 1 minute before the test
can be started again.
908.xxx Error [908.xxx] Device shut down.
Reason: Internal power failure on the measurement interface module.
Solution: The message is active as long as the internal power for the measurement interface fails.
Contact the next OMICRON service center if the error does not disappear.
911.xxx Error [911.xxx] Power supply error, contact next Omicron service center. Desired voltage xxxx,
measured voltage yyyy.
Reason: One supply voltage on the measurement interface boards is out of tolerance.
Solution: Contact your next OMICRON service center.
Comment: It is no longer possible to work with the device.
912.xxx Error [912.xxx] Excess internal temperature, wait until device has cooled down.
Reason: Device-internal temperature at measurement interface > 75°C.
Solution: Excessive heating of the device. Prevent the device from direct sunlight and wait until it has
cooled down. If the error occurs without previous exposure to direct sunlight, the error is
probably caused by a hardware error. Please contact your next OMICRON service center.
Comment: The status line displays the flashing message "912.xxx Overtemp.".
Safety action: All measurements are stopped and the error is displayed in the status line and in a popup
window. The error is active until the temperature falls below 60°C.
929.xxx Error [929.xxx] Hardware failure, contact next Omicron service center.
Reason: The circuit for reverse power dissipation does not work properly.
Solution: Contact your next OMICRON service center.
Safety action: All measurements are stopped and the power supply is switched off.
930.xxx Error [930.xxx] Measurement input Vsec defective, contact next Omicron service center.
Reason: Power supply for analog input "Sec" is defective.
Solution: Contact your next OMICRON service center.
931.xxx Error [931.xxx] Measurement input Vprim defective, contact next Omicron service center.
Reason: Power supply for analog input "Prim" is defective.
Solution: Contact your next OMICRON service center.
932.xxx Error [932.xxx] Data error.
Reason: The sequence of reading of the analog input channels is not correct.
Solution: If this error occurs more frequently, contact your next OMICRON service center.
933.xxx Error [933.xxx] Hardware failure, contact next Omicron service center.
Reason: Temperature detection circuit on secondary side is defective.
Solution: Send the device to your next OMICRON service center.
Safety action: Power supply is switched off and all measurements are disabled.