Loading...
9-25
9 Using Expansion Units and Expansion I/O Units
CP1E CPU Unit Hardware User’s Manual(W479)
9-3 Analog I/O Units
9
9-3-3 Specifications
z Analog Output Signal Ranges
-10 to 10 V
The hexadecimal values F448 to 0BB8 (-3000 to 3000) correspond to an analog voltage range of
-10 to 10 V.
The entire output range is -11 to 11V.
Specify the DA conversion data as the two’s complement if it is a negative value.
0 to 10 V
The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog voltage range of 0 to 10 V.
The entire output range is -0.5 to 10.5 V.
Specify the DA conversion data as the two’s complement if it is a negative value.
1 to 5 V
The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog voltage range of 1 to 5 V.
The entire output range is 0.8 to 5.2 V.
0 V
10 V
11 V
11 V
10 V
F448
(3000)
F31C
(3300)
0CE4
(3300)
0BB8
(3000)
0000 (0)
8000
7FFF
Conversion Data
Hexadecimal (Decimal)
0 V
10 V
10.5 V
0.5 V
FED4
(300)
189C
(6300)
1770
(6000)
0000 (0)
8000
7FFF
Conversion Data
Hexadecimal (Decimal)
1 V
5 V
5.2 V
0.8 V
189C
(6300)
1770
(6000)
0 V
7FFFFED4
(300)
8000
Conversion Data
Hexadecimal (Decimal)