EasyManua.ls Logo

Omron CP1E Series - Other Functions

Omron CP1E Series
260 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9 Using Expansion Units and Expansion I/O Units
9-26
CP1E CPU Unit Hardware User’s Manual(W479)
0 to 20 mA
The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog current range of 0 to 20 mA.
The entire output range is 0 to 21 mA.
4 to 20 mA
The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog current range of 4 to 20 mA.
The entire output range is 3.2 to 20.8 mA.
z Averaging Function for Analog Inputs
The averaging function can be enabled for inputs using the DIP switch. The averaging function out-
puts the average (a moving average) of the last eight input values as the converted value.
Use this function to smooth inputs that vary at a short interval.
z Open-circuit Detection Function for Analog Inputs
The open-circuit detection function is activated when the input range is set to 1 to 5 V and the volt-
age drops below 0.8 V, or when the input range is set to 4 to 20 mA and the current drops below
3.2 mA.
When the open-circuit detection function is activated, the converted data will be set to 8,000.
The time for enabling or clearing the open-circuit detection function is the same as the time for con-
verting the data.
If the input returns to the convertible range, the open-circuit detection is cleared automatically and
the output returns to the normal range.
Other Functions
0 mA
20 mA
21 mA
0000 (0)
189C
(6300)
1770
(6000)
7FFF
8000
Conversion Data
Hexadecimal (Decimal)
4 mA
20 mA
20.8 mA
3.2 mA
189C
(6300)
1770
(6000)
0 mA
7FFF
FED4
(300)
8000
Conversion Data
Hexadecimal (Decimal)

Table of Contents