9 Using Expansion Units and Expansion I/O Units
9-42
CP1E CPU Unit Hardware User’s Manual(W479)
2
#7FFF
W0.00
CMP
(P_EQ)
W0.00
002
#7FFE
Always ON
P_On
CMP
(P_EQ)
W0.01
3
#7FFE
Always ON
P_On
CMP
Detects completion of input 1 initialization.
(P_EQ)
W0.02
2
#1388
CMP
(P_GT)
W0.03
(P_LT)
2
D0
BCD
3
#7FFF
W0.01
CMP
(P_EQ)
W0.04
3
#1388
CMP
(P_GT)
W0.05
(P_LT)
3
D1
BCD
Detects completion of input 0 initialization.
ON when input 0 has been initialized
ON when input 1 has been initialized
Execution condition
Detects an open-circuit alarm or Unit
error by checking converted temperature
data for the error code 7FFF.
ON when an open-circuit alarm or Unit
error has been detected for input 0.
Checks to see if the temperature data
in word 2 has exceeded 500.0°C (1388
hex without decimal point).
ON for an input 0 temperature error
Converts the temperature data for
input 0 to BCD and stores the result in
D0.
Execution condition
Detects an open-circuit alarm or Unit
error by checking whether the error
code 7FFF has been output.
ON when an open-circuit alarm or Unit
error has been detected for input 1.
Checks to see if the temperature data
in word 3 has exceeded 500.0°C
(1388 hex without decimal point).
ON for an input 1 temperature error
Converts the temperature data for
input 1 to BCD and stores the result in
D1.