26
Interrupt Functions Section 1-4
Count Input Signal (Counter Mode) Wiring Example
PC Setup Parameters Before executing the program, make the following settings in the PC Setup in
PROGRAM mode.
Interrupt Input Settings (DM 6628)
If these settings are not made, interrupts cannot be used in the program.
Input Refresh Word Settings (DM 6630 to DM 6633)
Make these settings when it is necessary to refresh inputs for input interrupt
or counter mode.
Example
If DM 6630 is set to 0100, IR 000 will be refreshed when a signal is received
for interrupt 0.
Note If input refreshing is not used, input signal status within the interrupt routine
will not be reliable. This includes even the status of the interrupt input bit that
activated the interrupt. For example, IR 00000 would not be ON in interrupt
Terminal Corresponding bit address Decrementing mode
B0 (IN0) IR 00000 Pulse inputs (4 inputs max.)
A0 (IN1) IR 00001
B1 (IN2) IR 00002
A1 (IN3) IR 00003
Count input signal
CPU Unit
Input interrupt 3 setting
Input interrupt 2 setting
Input interrupt 1 setting
Input interrupt 0 setting
0: Normal input
1: Interrupt input
Default: All normal inputs.
15 0
DM 6628
Bit
Number of words (2-digit BCD) 00 to 16
Beginning word (2-digit BCD) 00 to 15
(IR 000 to IR 015)
Default: No input refresh
15 0
Bit
DM 6630: Interrupt 0
DM 6631: Interrupt 1
DM 6632: Interrupt 2
DM 6633: Interrupt 3
DM 6630 to DM 6633

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CQM1H - PROGRAM and is the answer not in the manual?

Omron CQM1H - PROGRAM Specifications

General IconGeneral
I/O CapacityUp to 512 points
Power Supply100 to 240 VAC, 50/60 Hz or 24 VDC (depending on model)
Instruction SetBasic and advanced instructions
Operating Temperature0 to 55°C
Program Capacity7.2K to 15.2K steps
Communication PortsRS-232C
Expansion SlotsUp to 3 expansion units
TypeProgrammable Logic Controller (PLC)
CPU TypeRISC
Program Memory7.2K to 15.2K steps
I/O Points512 max
Expansion CapabilityUp to 3 expansion units
Data MemoryRAM (battery backup)

Related product manuals