71
High-speed Counter Board Section 2-1
Reset Methods The following two methods can be set to determine the timing at which the PV
of the counter is reset (i.e., set to 0):
• Phase-Z signal + software reset
• Software reset
Phase-Z Signal (Reset Input) + Software Reset
The PV of the high-speed counter is reset in the first rising edge of the phase-
Z signal after the corresponding High-speed Counter Reset Bit (see below)
turns ON.
Software Reset
The PV is reset when the High-speed Counter Reset Bit turns ON. There are
separate Reset Bits for each high-speed counter 1 to 4.
The Reset Bits of high-speed counters 1 to 4 are given in the following table.
Reset Bits for high-speed counters 1 to 4 are refreshed only once each cycle.
A Reset Bit must be ON for a minimum of 1 cycle to be read reliably.
Note The comparison table registration and comparison execution status will not be
changed when the PV is reset. If a comparison was being executed before the
reset, it will continue.
Checking Methods for
High-speed Counter
Interrupts
The following two methods are available to check the PV of high-speed
counters 1 to 4. (These are the same methods as those used for built-in high-
speed counter 0.)
• Target value method
• Range comparison method
Refer to page 36 for a description of each method.
For the target value method, a maximum of 48 target values can be registered
in the comparison table. When the PV of the counter matches one of the 48
Phase-Z
(reset input)
1 or more cycles
1 or more cycles
Reset by interrupt.
Within 1 cycle
Reset by cycle. Not reset.
High-speed Counter
Reset Bit
Counter Reset Bit
Slot 1 Slot 2
High-speed counter 1 IR 21200 AR 0500
High-speed counter 2 IR 21201 AR 0501
High-speed counter 3 IR 21202 AR 0502
High-speed counter 4 IR 21203 AR 0503
Reset by cycle.
Within 1 cycle
1 or more cycles
High-speed Counter
Reset Bit