104
Variable Area Map Section 5-10
C3 012F - Auxiliary output 3 alloca-
tion (See note 2.)
00000000H (0): Heating control output for ch1
00000001H (1): Cooling control output for heating/cooling con-
trol for ch1
00000002H (2): Alarm 1 and sensor error alarm OR output for
ch1
00000003H (3): Alarm 2 output for ch1
00000004H (4): Alarm 3 output for ch1
00000005H (5): Heating control output for ch2
00000006H (6): Cooling control output for heating/cooling con-
trol for ch2
00000007H (7): Alarm 1 and sensor error alarm OR output for
ch2
00000008H (8): Alarm 2 output for ch2
00000009H (9): Alarm 3 output for ch2
0000000AH (10): SP transfer output for ch1
0000000BH (11): Ramp SP transfer output for ch1
0000000CH (12): PV transfer output for ch1
0000000DH (13): Heating MV transfer output for ch1
0000000EH (14): Cooling MV transfer output for ch1
0000000FH (15): SP transfer output for ch2
00000010H (16): Ramp SP transfer output for ch2
00000011H (17): PV transfer output for ch2
00000012H (18): Heating MV transfer output for ch2
00000013H (19): Cooling MV transfer output for ch2
0130 Auxiliary output 4 alloca-
tion (See note 2.)
Same as for auxiliary output 3 allocation
0131 OUT1 transfer output
upper limit (See note 2.)
FFFFF831H to 0000270FH (−1,999 to 9,999 or −199.9 to 999.9)
0132 OUT1 transfer output
lower limit (See note 2.)
FFFFF831H to 0000270FH (−1,999 to 9,999 or −199.9 to 999.9)
0133 OUT2 transfer output
upper limit (See note 2.)
FFFFF831H to 0000270FH (−1,999 to 9,999 or −199.9 to 999.9)
0134 OUT2 transfer output
lower limit (See note 2.)
FFFFF831H to 0000270FH (−1,999 to 9,999 or −199.9 to 999.9)
0135 SUB3 transfer output
upper limit (See note 2.)
FFFFF831H to 0000270FH (−1,999 to 9,999 or −199.9 to 999.9)
0136 SUB3 transfer output
lower limit (See note 2.)
FFFFF831H to 0000270FH (−1,999 to 9,999 or −199.9 to 999.9)
0137 SUB4 transfer output
upper limit (See note 2.)
FFFFF831H to 0000270FH (−1,999 to 9,999 or −199.9 to 999.9)
0138 SUB4 transfer output
lower limit (See note 2.)
FFFFF831H to 0000270FH (−1,999 to 9,999 or −199.9 to 999.9)
0139 Current output type
(See note 2.)
00000000H(0): 4 to 20 mA DC
00000001H(1): 0 to 20 mA DC
013A Voltage output type
(See note 2.)
00000000H(0): 1 to 5 VDC
00000001H(1): 0 to 5 VDC
013B Sensor error indicator
used
(See note 3.)
00000000H(0): Indicators always not lit.
00000001H(1): Sensor error indicator lit (ch1 only)
00000002H(2): Sensor error indicator lit (ch2 only)
00000003H(3): Sensor error indicator lit (ch1 or ch2)
013D Input error output
(See note 3.)
00000000H(0): OFF
00000001H(1): ON
013E Input shift type
(See note 3.)
00000000H(0): One-point temperature input shift
00000001H(1): Two-point temperature input shift
Variable
type
Address ch Setting data name Description