Variable Area Map Section 5-10
C3 012F - Auxiliary output 3 alloca-
tion (See note 2.)
00000000H (0): Heating control output for ch1
00000001H (1): Cooling control output for heating/cooling con-
trol for ch1
00000002H (2): Alarm 1 and sensor error alarm OR output for
ch1
00000003H (3): Alarm 2 output for ch1
00000004H (4): Alarm 3 output for ch1
00000005H (5): Heating control output for ch2
00000006H (6): Cooling control output for heating/cooling con-
trol for ch2
00000007H (7): Alarm 1 and sensor error alarm OR output for
ch2
00000008H (8): Alarm 2 output for ch2
00000009H (9): Alarm 3 output for ch2
0000000AH (10): SP transfer output for ch1
0000000BH (11): Ramp SP transfer output for ch1
0000000CH (12): PV transfer output for ch1
0000000DH (13): Heating MV transfer output for ch1
0000000EH (14): Cooling MV transfer output for ch1
0000000FH (15): SP transfer output for ch2
00000010H (16): Ramp SP transfer output for ch2
00000011H (17): PV transfer output for ch2
00000012H (18): Heating MV transfer output for ch2
00000013H (19): Cooling MV transfer output for ch2
0130 Auxiliary output 4 alloca-
tion (See note 2.)
Same as for auxiliary output 3 allocation
0131 OUT1 transfer output
upper limit (See note 2.)
FFFFF831H to 0000270FH (1,999 to 9,999 or 199.9 to 999.9)
0132 OUT1 transfer output
lower limit (See note 2.)
FFFFF831H to 0000270FH (1,999 to 9,999 or 199.9 to 999.9)
0133 OUT2 transfer output
upper limit (See note 2.)
FFFFF831H to 0000270FH (1,999 to 9,999 or 199.9 to 999.9)
0134 OUT2 transfer output
lower limit (See note 2.)
FFFFF831H to 0000270FH (1,999 to 9,999 or 199.9 to 999.9)
0135 SUB3 transfer output
upper limit (See note 2.)
FFFFF831H to 0000270FH (1,999 to 9,999 or 199.9 to 999.9)
0136 SUB3 transfer output
lower limit (See note 2.)
FFFFF831H to 0000270FH (1,999 to 9,999 or 199.9 to 999.9)
0137 SUB4 transfer output
upper limit (See note 2.)
FFFFF831H to 0000270FH (1,999 to 9,999 or 199.9 to 999.9)
0138 SUB4 transfer output
lower limit (See note 2.)
FFFFF831H to 0000270FH (1,999 to 9,999 or 199.9 to 999.9)
0139 Current output type
(See note 2.)
00000000H(0): 4 to 20 mA DC
00000001H(1): 0 to 20 mA DC
013A Voltage output type
(See note 2.)
00000000H(0): 1 to 5 VDC
00000001H(1): 0 to 5 VDC
013B Sensor error indicator
used
(See note 3.)
00000000H(0): Indicators always not lit.
00000001H(1): Sensor error indicator lit (ch1 only)
00000002H(2): Sensor error indicator lit (ch2 only)
00000003H(3): Sensor error indicator lit (ch1 or ch2)
013D Input error output
(See note 3.)
00000000H(0): OFF
00000001H(1): ON
013E Input shift type
(See note 3.)
00000000H(0): One-point temperature input shift
00000001H(1): Two-point temperature input shift
Variable
type
Address ch Setting data name Description