Variable Area Map Section 5-10
C3 011A 2 SP ramp setting 00000000H (0): OFF
00000001H to 0000270FH (1 to 9,999)
011B - Standby sequence restart 00000000H (0): Condition A
00000001H (1): Condition B
011C 2 Alarm 1 open in alarm 00000000H (0): Closed
00000001H (1): Open
011D Alarm 1 hysteresis 00000001H to 0000270FH (0.1 to 999.9)
011E Alarm 2 open in alarm 00000000H (0): Closed
00000001H (1): Open
011F Alarm 2 hysteresis 00000001H to 0000270FH (0.1 to 999.9)
0120 Alarm 3 open in alarm 00000000H (0): Closed
00000001H (1): Open
0121 Alarm 3 hysteresis 00000001H to 0000270FH (0.1 to 999.9)
0122 - Use heater burnout (See
note 1.)
00000000H (0): OFF
00000001H (1): ON
0123 Heater burnout latch
(See note 1.)
00000000H (0): OFF
00000001H (1): ON
0124 2 Heater burnout hystere-
sis (See note 1.)
00000001H to 000001F4H (0.1 to 50.0)
0125 - α 00000000H to 00000064H (0.00 to 1.00)
0126 2 MV upper limit Standard: Manipulated variable lower limit + 0.1 to 0000041AH
(manipulated variable lower limit + 0.1 to 105.0)
Heating/cooling: 00000000H to 0000041AH (0.0 to 105.0)
0127 MV lower limit Standard: FFFFFFCEH to manipulated variable upper limit 0.1
(5.0 to manipulated variable upper limit 0.1)
Heating/cooling: FFFFFBE6H to 00000000H (105.0 to 0.0)
0128 Input digital filter 00000000H to 0000270FH (0.0 to 999.9)
0129 - Additional PV display 00000000H (0): OFF
00000001H (1): ON
012A Temperature input offset
display add
00000000H (0): OFF
00000001H (1): ON
012B 2 Alarm 1 latch 00000000H (0): OFF
00000001H (1): ON
012C Alarm 2 latch 00000000H (0): OFF
00000001H (1): ON
012D Alarm 3 latch 00000000H (0): OFF
00000001H (1): ON
012E - Cold junction compensa-
tion method
00000000H (0): OFF
00000001H (1): ON
Variable
type
Address ch Setting data name Description