Sensor values and setting alarm algorithm for the Analog heat
detector 3308 / 3309:
According to chapter
"Access", see page 92.
Present system status on display and
printer ACCEPT? H4
Disablement
Printout: (1=yes) U1
Sensor values
Printout: (1=yes) U5
To make a printout, press
"1", else press "A" to
accept.
Enter technical number: 000000
Write the sensor's techn.
number and/or press "A"
to accept.
Sensor: 000003 Min: XX°C
Momentary: XX°C Max: XX°C
This is a list in which
you can scroll or use
"" to see the next
information window for
the selected sensor. Press
"Return" to Enter
technical number.
Sensor: 000003
Current algorithm: A1
A1 = short name, see
separate table, page 115.
Press "Return" to Enter
technical number or
press "Access" to change
the algorithm.
If login was made with
code for level 3, no code
is needed.
Enter code for level 3 (4
digits)
The digits are replaced
(****) in the display
Change algorithm: (000003 Current A1)
A1 A2 B
Change algorithm: (000003 Current A1)
A1 A2 B
Algorithm for sensor 000003 is changed
from A1 to B