Panasonic Eco Solutions Nordic AB
MEW01457 Rev: - Operating Instructions Fire alarm system EBL512, V2.7.x
120
Sensor values and setting alarm algorithm for the Analog heat
detector 3308 / 3309:
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 92.
Scroll to menu H4.
Present system status on display and
printer ACCEPT? H4
"A"
Disablement
Printout: (1=yes) U1
Scroll to menu U5.
Sensor values
Printout: (1=yes) U5
To make a printout, press
"1", else press "A" to
accept.
"A"
Enter technical number: 000000
Write the sensor's techn.
number and/or press "A"
to accept.
"A"
Sensor: 000003 Min: XX°C
Momentary: XX°C Max: XX°C
This is a list in which
you can scroll or use
"" to see the next
information window for
the selected sensor. Press
"Return" to Enter
technical number.
""
Sensor: 000003
Current algorithm: A1
A1 = short name, see
separate table, page 115.
Press "Return" to Enter
technical number or
press "Access" to change
the algorithm.
"Access"
Access code: _
If login was made with
code for level 3, no code
is needed.
Enter code for level 3 (4
digits)
Access code: ****
The digits are replaced
(****) in the display
Change algorithm: (000003 Current A1)
A1 A2 B
Use "" or "".
""
""
Change algorithm: (000003 Current A1)
A1 A2 B
"A"
Algorithm for sensor 000003 is changed
from A1 to B