Display menu - Configuration
Operating Manual PNOZ s30
1001715-EN-19
| 73
Level Designation
on the display
Description Settings
3 Track AB Tol
Default:
Off
Enter tolerance time for invalid
signal level on tracks A and B.
On encoder types with Z-index,
this tolerance time is also effect-
ive on track Z.
} Off
} 50 ms … 2500 ms
2 Track Z Settings for track Z
3 Track Z fmax
Default:
10mHz
Enter max. frequency of the en-
coder on track Z
Important:
The frequency must be less
than the max. encoder fre-
quency specified in the en-
coder's data sheet
10 mHz … 1.00 MHz
2 AB/fZ Ratio
Default:
1.0000: 1
Only required with 2 encoder
diagnostics/broken shearpin
monitoring or rotary encoder
with Z-index.
} 2 encoder diagnostics and
broken shearpin monitoring
Enter the ratio of the fre-
quency on tracks AB "fAB" to
the frequency on track Z "fZ".
Used for frequency monitoring
on track Z
Information
Calculation of the ratio of the
frequencies:
Enter permanent display: "vz:
v: Position:"
Switch on drive
Read vz and v
Divide v/vz
Enter result as fAB to fZ ratio
} Rotary encoder with Z index
The value fAB/fZ Verh. cor-
responds to the number of
lines (resolution) on the en-
coder you are using (lines/re-
volution).
Used to check the Z-index.
0.0001 ... 400,000: 1