Page 130 
Stopping 
P1 and P2 
If required, this feature will prevent pumps, with a common “OFF” point 
being switched off all at the same time pumps will be switched “OFF” in 
turn as determined by the delay set in P348 Stop Delay.  
P*348 Stop Delay 
Set the required time period, in seconds, that should elapse between pumps 
stopping. Default = 0.0 seconds. 
Pump Exercising 
P1 and P2 
This feature is used to reduce idle pump corrosion and sediment build up. 
Pumps  are  allowed  to  run  after  a  specified  Idle  Time  (P355)  for  a 
determined period of  Exercise time (P356),  providing a  Minimum head 
/level (P357) is present and all other pumps are switched off. 
P*354 Exercise Enable 
This parameter determines if Pump Exercising is enabled or disabled. 
 
P*355 Idle Time 
Sets the Idle Time to elapse before Pump Exercising is to be activated. 
Set the required time period in minutes. Default = 720 minutes 
P*356 Exercise Time 
Set the required Exercise Time in seconds. Default = 30 seconds 
P*357 Minimum Head 
To prevent the dry running and the possibility of cavatation, of the pump, 
enter the minimum level (head) of material, in measurement units (P*104), 
that is to be present before permitting pump exercising to take place.