Page 179 
P1-853, P2-853 Allocation 
This  parameter  determines  which  transducer  is  used  to  measure  the 
temperature when P1-852, P2-852 = 1 (Automatic) or 2 (Xducer) 
 
P1-854, P2-854 Fixed Temperature  
This parameter sets the temperature, in degrees centigrade to be used if P1-
852, P2-852 (Temperature Source) = 3 (Fixed). Default = 20
o
C 
Velocity 
P1 or P2 
P1-860, P2-860 Sound Velocity 
This parameter allows for the velocity of sound to be changed according to 
the atmosphere the transducer is operating in. By default the velocity is set 
for  sound  travelling  in  air  at  an  ambient  temperature  of  20  degrees 
centigrade. Default = 342.72m/sec 
P1-861, P2-861 Cal.Dist 
This parameter is used  to  re-calibrate  the speed  of  sound for the relevant 
point of measurement. 
With the material at a steady level, view the value of P1-861 or P2-862, 
which will indicate the current distance as calculated by the Ultra Twin 
with respect to the  current  Velocity P1-860, P2-860. Physically measure 
the distance from the face of the transducer to the surface of the material 
level  and  enter  this  value,  in  Measurement  Units  P*104  and  P1-860,  
P2-860  will  be  automatically  updated  to  compensate  for  any  difference 
between the displayed and entered values.