Page 170 
Setpoint 
P1 and P2 
By default the mA output will represent the empty (0 or 4mA) dependant 
on P*830 (mA Range) and 100% of the operational span (20mA), but you 
may wish to have the output represent a section of the operational span. For 
example, the application has an operational span of 20 feet but output is to 
represent empty (0 or 4mA) dependant on P*830 (mA Range) to a level of 
15 feet (20mA). If so P*834 (Low Value) should be set to 0.00 feet and 
P*835 (High Value) should be set to 15 feet.  
P*834 mA1 Low Value 
This parameter sets, in Measurement Units (P*104), the value of ‘level’, 
‘distance’ or ‘space’, depending on the selected mA Out Mode (P*831) at 
which the low mA output will occur (0 or 4mA dependant on (P*830) mA 
Range)    
Default = 0.000 feet 
P*835 mA1 High Value 
This parameter sets, in Measurement Units (P*104), the value of ‘level’, 
‘distance’ or ‘space’, depending on the selected mA Out Mode (P*831) at 
which the high mA output will occur (20mA).                                                           
Default = 19.685 feet 
Limits 
P1 and P2 
P*836 mA1 Low Limit 
This parameter sets the lowest  value that the mA output will drop to, the 
default is 0mA, but you can override this if the device you connect to cannot 
for example accept less than 2mA, yet you want to use the 0-20mA range. 
Default = 0.00mA 
P*837 mA1 High Limit 
This parameter sets the highest value that the mA output will rise to, the 
default is 20 mA, but you can override this if the device you connect to 
cannot for example accept more than 18 mA, yet you want to use the 0-20 
mA range.           
Default = 20.00mA