This  option  initiates  a  connection  to  a 
remote  modem/computer  which  will  then 
allow remote communication with the unit. 
Please  consult  Pulsar  or  your  local 
distributor for further details. 
This  option  initiates  a  predetermined 
message  which  is  sent  to  the  remote 
telephone  number  detailing  date  and  time 
the  alarm  was  initiated,  the  site  ID,  alarm 
condition  and  level  at  the  time  the  alarm 
was initiated.  
 
Test Parameters 
Simulation 
P1 or P2 
P1-980, P2-980 Simulate 
Test mode is used to simulate the application and confirm that all parameters 
and relay setpoints have been entered as expected. During simulation, there 
is a choice of whether the relays will change state (hard simulation) or not 
(soft simulation), but the LED’s will always change colour as programmed, 
and  the  current  output  will  change.  If  you  want  to  test  the  logic  of  the 
system that the relays are connected to then select a hard simulation, but if 
you don’t want to change the relay state, then select a soft simulation. 
There  are  two  simulation  modes,  automatic  and  manual.  Automatic 
simulation will move the level up and down between empty level or the pre-
determined Start Level (P1-983, P2-983) and Pump/Control  relay switch 
points, if you wish to change the direction of the level movement e.g. to go 
beyond relay setpoints, this can be done by using the arrow keys. In manual 
simulation, using the arrow keys will allow you to move the level up and 
down as required.