Factory Defaults 
When first installing the Ultra Twin, or subsequently moving or 
using the unit on a new application, before proceeding to program 
the unit for its intended application it is recommended that you 
ensure that all parameters are at their default values by completing a 
Factory Defaults P*930, as described in the relevant unit type 
parameter guide.  
 
 
When you  first switch the Ultra Twin on, it will be reading the distance 
from the face of the transducer to the surface. It will be indicating in feet, as 
shown on the display. All relays are set OFF. 
The  date  (P*931)  and  time  (P*932)  in  the  Ultra  Twin  were  set  at  the 
factory,  but  may  need  checking,  and  amending  if,  for  example  the 
application is in a time zone other than GMT, see relevant unit Parameter 
listing for full details.  
 TIP 
In some applications it is simplest to empty the 
vessel, take a reading from the Ultra Twin for 
distance and then setup the empty level to this 
figure. 
 
Once you are satisfied with the installation, and the Ultra Twin is reading 
what you would expect in terms of distance from the face of the transducer 
to  the  material  level,  then  you  can  proceed  with  programming,  for  the 
intended application. It is sensible to program all of the required parameters 
at the same time. The system will be then set-up.  
Note that the span is automatically calculated from the empty level, so the 
empty level should be entered first.