Page 140 
P*305 Input Filter 
This  parameter  is  used  to ignore  spurious  changes  of  state  on  the  digital 
inputs and determines the time that a change of state has to be present before 
it is recognised as a valid input. 
Enter the required filter time in seconds. Default = 1 second. 
Digital Inputs 
P1 and P2 
The Twin provides 4 Digital Inputs on the Wallmount model and seven on 
the Facsia model. 
The following parameters are used to configure the use of the digital inputs.  
P*372, P*375, P*378, P*381, P*384, P*387, P*390 - Type 
Determines the way digital inputs will be recognised by the Ultra Twin. 
Ultra Twin recognises a  closed  condition, 
D.C.  signal  voltage  present  at  the input, 
as a healthy/run condition. 
Ultra Twin recognises an open condition, 
D.C.  signal  voltage  not  present  at  the 
input, as a healthy/run condition. 
 
P*373, P*376, P*379, P*382, P*385, P*388, P*391 - Function 
This parameter will set the function of the digital Input. 
Digital  input  is  used  to  Fail,  (put  out  of 
service),  a  device  connected  to  the  relay 
specified  in  P*374,  377,  380,  383,  386, 
389, 392 Assignment.  
Digital  input  is  used  to  select  the  device, 
(pump), connected to the relay specified in 
P*374,  377,  380,  383,  386,  389,  392 
Assignment  as  the  current  duty  device 
(pump).