Page 141
Option
Description
3 = Override On
Digital input is used to provide a signal to
instigate an Override and switch all Pump
relays “ON”, as determined by P*374, 377,
380, 383, 386, 389, 392 (Assignment),
P*302 (Override Delay) and P*303 (Min.
Override).
4 = Override Off
Digital input is used to provide a signal to
instigate an Override and switch all Pump
relays OFF”, as determined by P*374,
377, 380, 383, 386, 389, 392
(Assignment), P*302 (Override Delay)
and P*303 (Min. Override).
5 = Reset.
(Wallmount Input 4 only)
(Fascia Input 7 only)
Input is used to Reset all Device Fail
conditions.
Alternatively the key can be used, whilst
the in RUN, to Reset any Device Fail.
6 = Inhibit Meas.
Input is used to inhibit the measurment of
the point it is allocated too as specified by
P*374, 377, 380, 383, 386, 389, 392
(Assignment).
P*374, P*377, P*380, P*383, P*386, P*389, P*392 Assignment
When P*373, 376, 379, 382, 385, 388, 391 = 1 (Device Fail) or 2 (Duty)
This parameter assigns the digital input to the appropriate device relay that
the Function, (P*373, 376, 379, 382, 385, 388, 391), is to be applied.
Option
Description
0 = None
Digital Input is not assigned to any relay.
1 = Relay 1 (Default)
Digital input is assigned to Device
connected to Relay 1.
2 = Relay 2
Digital input is assigned to Device
connected to Relay 2.
3 = Relay 3
Digital input is assigned to Device
connected to Relay 3.
4 = Relay 4
Digital input is assigned to Device
connected to Relay 4.
5 = Relay 5
Digital input is assigned to Device
connected to Relay 5.
6 = Relay 6
Digital input is assigned to Device
connected to Relay 6.