Page 132 
Digital Inputs 
About Digital Inputs 
The  digital  inputs  are  used  to  provide  the  Twin  with  information  on  the 
operational status and condition of pumps, valves, and other process control 
devices. Based  on the information supplied,  by the  inputs, the Twin, will 
make intelligent decisions and modify its control regime to meet the demand 
of the prevailing operational requirements. 
The parameters used to program the Digital inputs are as follows: 
Common Parameters P*300 to P*306 
Digital Input 1 P*372 to 374  Digital Input 2 P*375 to 377 
Digital Input 3 P*378 to 380  Digital Input 4 P*381 to 383 
Digital Input 5 P*384 to 386  Digital Input 6 P*387 to 389 
Digital Input 7  P*390 to 392 
 
Common Parameters Set-up 
These parameters determine specific operational criteria for particular digital 
input functions and are common to each digital input.  
Input Type 
The digital inputs can be either voltage source, where Twin will supply the 
switching voltage, or voltage synch, where the switching voltage is supplied 
by the input from the device,  for  full details see  Chapter 2  Installation. 
Both voltage source and voltage synch. inputs can be configured for N.O. or 
N.C. operation as determined by the digital input  Type P*372, 375, 378, 
381,  384,  387,  390  when  set  to  1=  Input  N.C.,  Twin  will  recognises  a 
closed  condition,  D.C.  signal  voltage  present  at  input,  as  a  healthy 
condition, alternatively, an open condition, D.C. signal voltage not present 
at input, indicating a healthy condition, can be chosen as a valid input by 
selecting 2=Input N.O.