Universal Curved (P1-600, P2-600 =12) 
This volume calculation creates a curved approximation of the level/volume 
relationship,  and  works  best  if  the  vessel  is  non-linear,  and  there  are  no 
sharp angles. 
     
 
You should enter 2 level/volume breakpoints at the minimum and maximum 
levels, and several for each place where the vessel has got an arc. You can 
enter any number of pairs between 2 and 32. 
 
Tables 
P1 or P2 
P1-696, P2-696 Reset Breakpoints 
This parameter allows the resetting, to the default value, of all previously set 
breakpoints (P1-610 to 673, P2-610 to 673), without having to access them 
individually. When it is necessary to reset or amend particular breakpoints 
this can be achieved by directly accessing the desired parameter (P1-610 to 
673, P2-610 to 673) and changing as required. 
P1-697, P2-697 Number of  Breakpoints Set 
This parameter allows you to review the number of breakpoints that have 
been set, without the need to access each individual one in turn, this is a 