Page 194 
The choices for you to enter are as follows. 
1= Manual soft simulation   
2= Automatic soft simulation   
3= Manual hard simulation   
4= Automatic hard simulation 
To return to program mode, press CANCEL and test mode will end. 
 
 
Test Setup 
P1 and P2 
P*981Increment 
By  default,  simulation  mode  will  move  by  0.328  feet  steps  in  manual 
simulation  and  by  0.328  feet/min  in  automatic  simulation.  Altering  the 
increment can change this value. 
P*982 Rate 
In automatic mode, the rate at which the level will move up and down, is 
determined by distance, P*981 Increment and the time, P*982 Rate which 
by default is set to 1min and can be changed as required. To increase the 
rate at which the level moves increase the Increment (P*981) or decrease 
the Rate (P*982). To decrease the rate at which the level moves decrease 
the Increment (P*981) or increase the Rate (P*982). 
P*983 Start Level 
When  using  automatic  simulation  this  parameter  can  be  used  to  pre-
determine the point at which the simulated level will start at and return to. 
This  can  be  used  to  simulate  the  lowest  point  to  which  the  level  would 
normally operate.