Page 194
The choices for you to enter are as follows.
1= Manual soft simulation
2= Automatic soft simulation
3= Manual hard simulation
4= Automatic hard simulation
To return to program mode, press CANCEL and test mode will end.
Note
Pump start delay (which by default is 10 seconds) is set to 0 during
simulation.
Test Setup
P1 and P2
P*981Increment
By default, simulation mode will move by 0.328 feet steps in manual
simulation and by 0.328 feet/min in automatic simulation. Altering the
increment can change this value.
P*982 Rate
In automatic mode, the rate at which the level will move up and down, is
determined by distance, P*981 Increment and the time, P*982 Rate which
by default is set to 1min and can be changed as required. To increase the
rate at which the level moves increase the Increment (P*981) or decrease
the Rate (P*982). To decrease the rate at which the level moves decrease
the Increment (P*981) or increase the Rate (P*982).
P*983 Start Level
When using automatic simulation this parameter can be used to pre-
determine the point at which the simulated level will start at and return to.
This can be used to simulate the lowest point to which the level would
normally operate.

Table of Contents

Other manuals for Pulsar ULTRA TWIN

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pulsar ULTRA TWIN and is the answer not in the manual?

Pulsar ULTRA TWIN Specifications

General IconGeneral
BrandPulsar
ModelULTRA TWIN
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals