Page 70
Exponential Devices
If the primary measuring device is a simple exponential device then an
exponent value is required. The Ultra Twin will automatically enter the
exponent value for the device chosen as detailed in the table below.
Exponent Type
Exponent
Suppressed Rectangular
Weir
1.50
Cipolletti (Trapezoidal) Weir
1.50
Venturi Flume
1.50
Parshall Flume
Default = 1.55
but value can be
set as required
via P717
Leopold Lagco Flume
1.55
V-Notch Weir
2.50
Other
As per manufacturer
Value to be set
as required via
P717