Page 131
Wall Cling
P1 and P2
To reduce material build up (such as fat), on the wall of the sump or vessel,
at the “normal” material level the pump setpoints can be varied within a
specified band.
For Pump Down applications the relay setpoints for the pumps will be
randomly varied within the band specified, somewhere below ON, but to a
maximum of the setting, and somewhere higher than OFF, but to a
maximum of the setting.
For Pump Up applications the relay setpoints for the pumps will be
randomly varied within the band specified somewhere higher than ON, but
to a maximum of the setting, and somewhere lower than OFF, but to a
maximum of the setting.
P*360 Wall Cling
Enter the maximum band, of variation, required in measurement units
(P*104).