Page 139 
P*301 Switch Mode 
When an external duty switch is used this can be connected via the digital 
inputs  and  facilitate  the  selection  of  the  duty  device  manually,  thereby 
overriding the duty programmed within the unit. 
This parameter determines the type of switch in use.  
A standard switch,  e.g.  rotary switch, can 
be  used  with  one  switch  position  and  a 
digital input required for each pump. 
To  reduce  the  number  of  digital  inputs 
used,  for  manual  duty  selection,  a  binary 
switch can be supplied. Max. No. of digital 
inputs required being three. 
 
P*302 Override Delay 
A digital input can be assigned to receive an input, which will override the 
setpoints of the pumps and start them, providing the level is above the Min. 
Override (P*303), immediately after the expiry of the Override Delay.  
Enter the required delay time in minutes. Default = 0.0 feet. 
P*303 Min Override 
Determines the minimum level required before an Override Delay (P*302) 
will be in effect. 
Enter the required level in Measurement Units (P*104).                    
Default = 0.0 feet. 
P*304 Input Delay 
This parameter determines the delay applied, from the time a device (relay) 
is called to “run” and when the status of the digital input is recognised as a 
valid  input.  If  the  digital  input  is  used  to  detect  a  “running”  signal  this 
parameter should be set to reflect the time it takes from the device being 
called to “run” to the input being in its operational status. 
Enter the required delay time in seconds. Default = 10 seconds.