Page 154
P1-703, P2-703 Minimum Head
This parameter is used to enter the distance, above empty, that represents
zero head and flow. This feature is used in Primary Measuring Devices
where the zero reference is at a higher level than the channel bottom, at the
point of measure. Enter distance in Measurement Units P*104.
P1-704, P2-704 Maximum Head
Enter the head value that represents maximum flow, enter in Measurement
Units P*104.
Note any change to the value of this parameter will be reflected in P1-106,
P2-106 (Span) and vice versa.
P1-705, P2-705 Maximum Flow
When P1-702, P2-702 = 2 Ratiometric enter the flow rate value that occurs
at maximum head (P1-704, P2-704), enter in volume units (P1-706, P2-
706) per time units (P1-707, P2-707).
When P1-702, P2-702 = 1 Absolute, and all relevant flow parameters have
been entered, the maximum flow that occurs at maximum head P1-704,
P2-704 will be calculated, after the unit is returned to RUN mode, and
displayed in this parameter in volume units (P1-706, P2-706) per time
units (P1-707, P2-707).
P1-706, P2-706 Volume Units
Select the Volume Units to be used to display and calculate the flow rate
from the options below: