To program the Ultra Twin for Example 2 Reservoir Control (pump up)
by using the Quick Setup menu proceed as follows.
If required access the Program Mode
Key in the passcode 1997 and press ENTER
At the Quick Setup menu press the hot key and toggle to Point 2 display
and press ENTER and then as prompted, by the questions, select the
relevant option and ENTER.
Question
Option
Application
2 = Pump
Level, Pump Up/Down
3 = Pump Up
No. of Pumps
2 = 2 Pumps
Pump Duty
3 = Alt DutAss
Pump No. 1
1 = Set to Relay 1
Pump No. 2
2 = Set to Relay 2
No. of Alarms
1 = 1 Alarm
Type Alarm 1
2 = Low
Alarm No.1
3 = Set to Relay 3
Xducer (P1-101)
2 = dB6
Measnt Units (P*104)
4 = feet
Empty Level (P1-105)
11.0 (feet)
Span (P1-106)
10.0 (feet)
Programming is now complete and the unit can be returned to the run mode,
press CANCEL until Run Mode? Is displayed on the LCD press ENTER,
and the Ultra Twin will return to the Run Mode.
Note
If relay setpoints do not meet the exact requirements of the
application, they can be modified to suit by pressing ENTER when,
“For More Options Hit Enter”, is displayed, and entering new values
to relay setpoints as required. Alternatively the relevant relay
setpoint can be accessed either by the main menu system or directly
via parameter number and changed as necessary.

Table of Contents

Other manuals for Pulsar ULTRA TWIN

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pulsar ULTRA TWIN and is the answer not in the manual?

Pulsar ULTRA TWIN Specifications

General IconGeneral
BrandPulsar
ModelULTRA TWIN
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals