NO. Parameter Name Setting Range Default
f904 PID control waiting time 0~2400s 0
When f904 is set to value > 0 s, the inverter will not enter into PID control immediately
after started. During the time set by f904, the inverter will ignore the feedback signal and
accelerate the motor to the speed set by the input setting.
NO. Parameter Name Setting Range
0~1 0
0: Disabled.
1: Enabled.
Note: PID regulator negation is performed in two ways: Make f905=1, or define logic
input function as 38 and the corresponding terminal is closed.
NO. Parameter Name Setting Range Default
f906
Sleep mode awakening hysteresis
bandwidth
0.0 Hz ~ f007 0.2
Under the sleeping mode, the inverter will re-accelerate the motor to the given frequency
once it detects frequency command > f009+f906. See f501 or f915.
NO. Parameter Name Setting Range Default
f907
Sleeping mode awakening threshold
based on PI deviation
0.0 Hz ~f007 0.0
Under the sleeping mode, the inverter will re-accelerate the motor to the given frequency
once it detects the error between PID setting and PID feedback > f907.
NO. Parameter Name Setting Range Default
f908
Sleeping mode awakening threshold
based on PI feedback
0.0 Hz ~f007 0.0
Under the sleeping mode, the inverter will re-accelerate the motor to the given frequency
once it detects the PID feedback > f908(when f905=0).
NO. Parameter Name Setting Range