0: Motor slowdown to a stop.
1: Motor keep running at the speed setting by f009.
NO. Parameter Name Setting Range Default
f910 wake up delay 0~600.0s 0.0
frequency
Hz
0
Run
command
OFF
times
ON
f 0 0 9
f 9 1 0
Operation
frequency
Frequency
command
Figure 2.39 description of wake up from sleep mode
NO. Parameter Name Setting Range Default
f911 Auto wake up level 0~100.0% 0.0
When feedback detected value is smaller than f911 setting, inverter wake up from sleep
mode.
NO. Parameter Name Setting Range
Default
f912 Auto sleep level 0~100% 0.0
When feedback detected value is bigger than f912 setting, inverter enter into sleep mode
and stop the motor.
NO. Parameter Name Setting Range
Default
f913 Upper limit of PID setting 0~100% 100
f914 Lower limit of PID setting 0~100% 0
f913 and
f914 set the upper and lower limit frequency that determines PID setting.
NO. Parameter Name Setting Range Default
f915
auto-stop time limit for lower-limit
frequency operation
0~600.0 0.1
See f501. Note:
f915 and
f501 are the same parameter internally.