B-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL
6 of 147
SECTION 2: INSTALLER RESPONSIBILITY
The installer is responsible for the following:
• To install and commission the air handler, as well
as the gas and electrical supplies, in accordance
with applicable specifications and codes. Rapid
Engineering LLC recommends the installer
contact a local building inspector or Fire Marshal
for guidance.
•To use the information given in a layout drawing
and in the manual together with the cited codes
and regulations to perform the installation.
• To install the heater in accordance with the
clearances to combustibles.
•To furnish all needed materials not furnished as
standard equipment.
• To plan location of supports.
• To provide access to
air handler
for servicing.
• To provide the owner with a copy of this
Installation, Operation and Service Manual.
• To never use heater as support for a ladder or
other access equipment and never hang or
suspend anything from heater.
•To ensure there is adequate air circulation around
the air handler and to supply air for combustion,
ventilation and distribution in accordance with
local codes.
• To assemble or install any accessories or
associated duct work using best building
practices.
• To properly size supports and hanging materials.
• To ensure heater is placed in an approved
application.
2.1 Wall Tag
A laminated wall tag is available for the heater as a
permanent reminder of the safety instructions and
the importance of the required clearances to
combustibles. Please contact Rapid Engineering LLC
or your RAPID
®
independent distributor to obtain the
wall tag. Affix the tag on a wall near the heater (e.g.
thermostat or control system).
A copy of the wall tag (P/N 91040118) is illustrated on
the back cover. For an immediate solution, you may
affix this copy on the wall near the heater.
Know your model number and installed configuration.
Model number and installed configuration are found
on the rating plate and in the Installation, Operation
and Service Manual. See Page 3, Figure 1 through
Page 4, Figure 3.
2.2 Corrosive Chemicals
Rapid Engineering LLC cannot be responsible for
ensuring that all appropriate safety measures are
undertaken prior to installation; this is entirely the
responsibility of the installer. It is essential that the
contractor, the sub-contractor, or the owner identifies
the presence of combustible materials, corrosive
chemicals or halogenated hydrocarbons* anywhere
in the premises.
* Halogenated Hydrocarbons are a family of chemical
compounds characterized by the presence of halogen elements
(fluorine, chlorine, bromine, etc.). These compounds are
frequently used in refrigerants, cleaning agents, solvents, etc. If
these compounds enter the air supply of the burner, the life span
of the air handler components will be greatly reduced. The loca-
tion of the outside air supply must be carefully chosen to supply
outside air, free of these compounds, to the burners whenever
the presence of these compounds is suspect. Warranty will be
invalid if the air handler is exposed to halogenated hydrocar-
bons.
WARNING
Explosion Hazard
Equipment must have access to
uncontaminated air at all times.
Failure to follow these instructions can result
in death, injury or property damage.
CAUTION
Product Damage Hazard
Do not use equipment in area containing
corrosive chemicals.
Refer to appropriate Material Safety Data
Sheets (MSDS).
Failure to follow these instructions can result
in product damage.