1. OUTLINE
IMR02C15-E4
1-6
Input Range Code Table
[Thermocouple input (Temperature input group)] * [Resistance temperature detector input (Temperature input group)] *
Type Code
Range
(Measured range)
Code
Range
(Measured range)
Type Code
Range
(Measured range)
Code
Range
(Measured range)
K01 0 to 200 °C K43 199.9 to +400.0 °C D01199.9 to +649.0 °C DA2 199.9 to +400.0 °F
K02 0 to 400 °C K09 0.0 to 400.0 °C D02 199.9 to +200.0 °C DA3 199.9 to +200.0 °F
K03 0 to 600 °C K10 0.0 to 800.0 °C D03 100.0 to +50.0 °C DA4 199.9 to +100.0 °F
K K04 0 to 800 °C KA1 0 to 800 °F D04 100.0 to +100.0 °C DA5 199.9 to +300.0 °F
K05 0 to 1000 °C KA2 0 to 1600 °F Pt100 D05 100.0 to +200.0 °C DA6 0.0 to 100.0 °F
K06 0 to 1200 °C KC7 328 to +2501 °F D06 0.0 to 50.0 °C DA7 0.0 to 200.0 °F
K41 200 to +1372 °C KC8 100.0 to +752.0 °F D07 0.0 to 100.0 °C DA8 0.0 to 400.0 °F
J01 0 to 200 °C J15 200 to +1200 °C D08 0.0 to 200.0 °C DA9 0.0 to 500.0 °F
J02 0 to 400 °C J07 199.9 to +300.0 °C D09 0.0 to 300.0 °C DB2 199.9 to +900.0 °F
J J03 0 to 600 °C JA1 0 to 800 °F D10 0.0 to 500.0 °C
J04 0 to 800 °C JA2 0 to 1600 °F P01 199.9 to +649.0 °C P06 0.0 to 50.0 °C
J05 0 to 1000 °C JB9 328 to +2192 °F P02 199.9 to +200.0 °C P07 0.0 to 100.0 °C
J06 0 to 1200 °C JC8 199.9 to +550.0 °F JPt100 P03 100.0 to +50.0 °C P08 0.0 to 200.0 °C
T T02 199.9 to +100.0 °C TC7 0.0 to 600.0 °F P04 100.0 to +100.0 °C P09 0.0 to 300.0 °C
T03 100.0 to +200.0 °C TC8 199.9 to +300.0 °F P05100.0 to +200.0 °C P10 0.0 to 500.0 °C
T05 199.9 to +300.0 °C TC9 328 to +752 °F
T06 0.0 to 400.0 °C
E E01 0 to 800 °C EA1 0 to 1600 °F
E02 0 to 1000 °C EA2 0 to 1832 °F
S S02 0 to 1769 °C SA2 0 to 3216 °F
R R02 0 to 1769 °C RA2 0 to 3216 °F
B B01 400 to 1800 °C BA1 800 to 3200 °F
[Voltage input/Current input (Voltage/Current input group)] *
B02 0 to 1820 °C BA2 0 to 3308 °F Type Code Range (Measured range)
N N01 0 to 1200 °C NA1 0 to 2300 °F
0 to 1 V DC
301
N02 0 to 1300 °C NA2 0 to 2372 °F
0 to 5 V DC
401 Programmable range
PLII A01 0 to 1300 °C AA1 0 to 2400 °F
0 to 10 V DC
501
1999 to +9999
A02 0 to 1390 °C AA2 0 to 2534 °F
1 to 5 V DC
601
[The decimal point position is selectable]
W5Re/W26Re W01 0 to 2000 °C WA4 0 to 4208 °F 0 to 20 mA DC ** 701
(Factory set value: 0.0 to 100.0 %)
W02 0 to 2320 °C 4 to 20 mA DC ** 801
* Universal input within each input group
** For current input, connect is a 250 shunt resistor to the input terminals.
Output 2 Code Table
Output type Code Remarks Output type Code Remarks
Relay contact output [Cool output] M Relay contact output [Event 3 output] P Only RB100 (PID control)
Voltage pulse output [Cool output] V
Voltage output (0 to 5 V DC)
[Cool output]
4 Current output (0 to 20 mA DC)
[Transmission output]
R
Voltage output (0 to 10 V DC)
[Cool output]
5 Current output (4 to 20 mA DC)
[Transmission output]
S
Voltage output (1 to 5 V DC)
[Cool output]
6 Voltage output (0 to 5 V DC)
[Transmission output]
X
Current output (0 to 20 mA DC)
[Cool output]
7 Voltage output (0 to 10 V DC)
[Transmission output]
Y
Only PID control
Current output (4 to 20 mA DC)
[Cool output]
8 Voltage output (1 to 5 V DC)
[Transmission output]
Z
Triac output [Cool output] T
Open collector output [Cool output] D

Table of Contents