5. SETUP PROCEDURES PRIOR TO RUNNING THE INSTRUMENT
IMR02C15-E4
5-11
To manually adjust the PID parameters
If the Autotuning (AT) function does not match the controlled object requirements, the optimum PID
values may not be calculated by Autotuning (AT). In that case, adjust the PID parameters manually.
Change the Proportional band (P)
[Example: Change the Proportional band (P) to 20 °C]
1. Press and hold the key for 2 seconds or more at the PV/SV monitor screen to go to the
Parameter setting mode, and press the key to display the Proportional band [heat-side] screen.
2. Press the , , and keys to change from “0015” to “0020.” Press the key to store
the new value.
Change the Integral time (I) and Derivative time (D)
The setting procedure applies when the Integral time and the Derivative time are also set.
Return to the PV/SV monitor
To return the PV/SV monitor, press
and hold the key for 2 seconds or more.
After a new value is displayed on the display by using and keys, if no key
operation is performed within 1 minute without pressing key, this instrument returns
to the PV/SV monitor screen and the set value will not be changed.
SET
SET
R/S
SET
SET
I
0240
SV1
OUT1
OUT
2
A
T
DO1 DO
2
MAN
STOP
DO3
DO4
D
0060
SV1
OUT1
OUT
2
A
T
DO1 DO
2
MAN
STOP
DO3
D
O
4
Integral time
Derivative time
Setting range:
1 to 3600 seconds
(0: PI action)
[Factory set value: 60]
Setting range:
1 to 3600 seconds
(0: PD action)
[Factory set value: 240]
28$
200
SV1
OUT1
OUT
2
A
T
DO1 DO
2
MAN
STOP
DO3
DO4
PV/SV monitor
SV1
$
0200
SV1
OUT1
OUT
2
A
T
DO1 DO
2
MAN
STOP
DO3
DO4
2 seconds or more
SET
Parameter setting mode
Set value 1 (SV1)
SET
Parameter setting mode
Proportional band [heat-side]
P$
0015
SV1
OUT1
OUT
2
A
T
DO1 DO
2
MAN
STOP
DO3
DO4
Press the key to Proportional
band [heat-side] screen (
P)
SET
Proportional band [heat-side]
Setting range:
TC/RTD input:
1 (0.1) to Input span (Unit: °C [°F])
[Resolution 0.1 °C (°F): Within 999.9 °C (°F)]
[Factory set value: 30 (30.0)]
Voltage (V)/Current (I) input:
0.1 to 100.0 % of Input span
[Factory set value: 3.0]
0 (0.0): ON/OFF action
P
$
0015
SV1
OUT1
OUT
2
A
T
DO1 DO
2
MAN
STOP
DO3
DO4
P
$
0010
SV1
OUT1
OUT
2
A
T
DO1 DO
2
MAN
STOP
DO3
DO4
P$
0010
SV1
OUT1
OUT
2
A
T
DO1 DO
2
MAN
STOP
DO3
DO4
R/S
P
$
0020
SV1
OUT1
OUT
2
A
T
DO1 DO
2
MAN
STOP
DO3
DO4
I
0240
SV1
OUT1
OUT
2
A
T
DO1 DO
2
MAN
STOP
DO3
DO4
SET
Flashing
Press the key to change the
number to 0 in the units digit.
Press the key to blink
the tens digit.
R/S
Press the key to
change the number to 2.
Press the key to store the
new value. The display goes to the
next parameter. (Integral time)
SET
SET

Table of Contents

Other manuals for RKC INSTRUMENT RB Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the RKC INSTRUMENT RB Series and is the answer not in the manual?

RKC INSTRUMENT RB Series Specifications

General IconGeneral
BrandRKC INSTRUMENT
ModelRB Series
CategoryTemperature Controller
LanguageEnglish

Related product manuals