10. SPECIFICATIONS
IMR02C15-E4
10-7
Control
Control method: PID control (Direct/Reverse action is selectable)
Heat/Cool PID control
P, PI, PD, or ON/OFF action is available
Additional function: Autotuning, Startup tuning, Fine tuning
PID control
Overshoot suppression function: Anti-reset windup (ARW)
Setting range: a) Proportional band [heat-side] (P) *
TC/RTD inputs: 1 (0.1) to Input span (unit: °C [°F])
Voltage/Current inputs: 0.1 to 100.0 % of Input span
* 0 (0.0): ON/OFF action
ON/OFF action differential gap:
TC/RTD inputs: 0 (0.0) to 100 (100.0) °C [°F]
Voltage/Current inputs: 0.0 to 10.0 % of Input span
b) Integral time (I): 1 to 3600 seconds (0: PD action)
c) Derivative time (D): 1 to 3600 seconds (0: PI action)
d) Anti-reset windup (ARW):
1 to 100 % of Proportional band [heat-side]
(0: Integral action OFF)
e) Derivative action: Measured value derivative,
Deviation derivative
f) Proportional cycle time: 0 to 100 seconds
(0: Setting below 1 second is possible for
“Time setting of proportional cycle time [heat-side]”)
g) Time setting of proportional cycle time [heat-side]:
0.1 second, 0.25 second, 0.5 second
h) Output limiter (high/low):
5.0 to +105.0 %
(High/Low individual setting) **
** Output limiter low < Output limiter high
i) Manual output: Output limiter low to Output limiter high