8. PARAMETER DESCRIPTION
IMR02C15-E4
8-122
Dummy
Function block 45 (F45)
This is the first parameter symbol of Function block 45 (F45).
The settings of parameters in this group are valid only when the CT input
(optional) function is specified.
In addition, digital output (optional) must be specified for the Heater break
alarm to function.
If the output 1 (OUT1) is current output or voltage output, the CT input
(optional) cannot be used.
F45
CT ratio (Number of turns)
Use to set the Number of turns in the current transformer used to monitor the
current flowing through the load. There are two types of dedicated current
transformers.
Data range Factory set value
1 to 1000 When the current transformer
type is CTL-6-P-N:
800
When the current transformer
type is CTL-12-S56-10L-N:
1000
Related parameters
Parameter setting mode:
• Heater break alarm 1 (HBA1) set value (P. 8-31)
• Heater break alarm 2 (HBA2) set value (P. 8-31)
Engineering mode:
• Number of HBA delay times (P. 8-123)
F45.
CTR

Table of Contents

Other manuals for RKC INSTRUMENT RB Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the RKC INSTRUMENT RB Series and is the answer not in the manual?

RKC INSTRUMENT RB Series Specifications

General IconGeneral
BrandRKC INSTRUMENT
ModelRB Series
CategoryTemperature Controller
LanguageEnglish

Related product manuals