3. WIRING
IMR02C15-E4
3-12
Measured input (Thermocouple/RTD/Voltage/Current) [universal input]
For the measured input type, terminals 10 through 12 (RB700: terminals 16 through 18) are
allocated to the measured input.
The input types (input group) are as follows.
Input group Input type
Thermocouple
K, J, T, S, R, E, B, N (JIS C1602-1995),
PLII (NBS), W5Re/W26Re (ASTM-E988-96)
Temperature input
group
RTD
Pt100 (JIS C1604-1997), JPt100 (JIS C1604-1997, JIS C1604-1981 Pt100)
Voltage (low) 0 to 1 V DC, 0 to 5 V DC, 1 to 5 V DC, 0 to 10 V DC
Voltage/current input
group
Current 0 to 20 mA DC, 4 to 20 mA DC
For thermocouple input, use the appropriate compensation wire.
For RTD input, use low resistance lead wires with no difference in resistance between the three
lead wires.
To avoid noise induction, keep input signal wire away from instrument power line, load lines and
power lines of other electric equipment.
For the current input specification, a shunt resistor of 250 ±0.02 % (Temperature characteristics:
±10 ppm/°C, Specified voltage: 0.25 W or more) must be connected between the input terminals.
Shunt resistor: Model code: KD100-55 (sold separately)
RTD input
10
11
12
RTD
A
B
B
Thermocouple input
TC
+
12
11
Voltage input
IN
+
12
11
Current input *
IN
+
12
11
* Shunt resistor KD100-55 (sold separately)
must be mounted between input terminals
RB100/400/500/900:
RTD input
16
17
18
RTD
A
B
B
Thermocouple input
TC
+
18
17
Voltage input
IN
+
18
17
Current input *
IN
+
18
17
* Shunt resistor KD100-55 (sold separately)
must be mounted between input terminals
RB700: