8. PARAMETER DESCRIPTION
IMR02C15-E4
8-94
Dummy
F21
PV flashing display at input error
It can also be set so that the PV display does not flash “1: Non-flashing
display.” The Measured value (PV) of this instrument flashes in the range of an
“input span of 5 %” if exceeding the input range.
Data range Factory set value
0: Flashing display
1: Non-flashing display
0
Example: When set to non-flashing display in the range of 0 to 800 °C
Input range
(Input scale low to Input scale high)
5
of input span (40 °C)
Non-flashing display
Display range limit (Non-flashing display)
Underscale
flashing display
Overscale
flashing display
−40 °C
0 °C
800 °C
840 °C
In
ut s
an: 800 °C
uuuu oooo
DSOP