5. SETUP PROCEDURES PRIOR TO RUNNING THE INSTRUMENT
5-6 IMR02C15-E4
5.2 Operation Setting
Set the control set value
After finishing the initial settings, set the control target value, SV.
[Setting example: Set the control set value 1 (SV1) to 200 °C.]
1. Make sure that the PV/SV monitor screen is displayed, and SV1 is selected (factory set value:
SV1), then press the key to go to the SV setting mode.
2. Change SV1 to 200 °C using the , and keys, then press the key to store the new set
value.
To set SV2, SV3 and SV4, or to set SVs using digital input,
refer to 7.1 SV Selection Function
(Step SV function) (P. 7-2).
SET
PV/SV monitor
28
$
0
SV1
28
$
0000
SV1
SV setting mode
Set value 1 (SV1)
SET
Check that the SV1
lamp lights.
Setting range:
Setting limiter low to Setting limiter high
[Factory set value: 0 (0.0)]
Set value 1 (SV1)
PV/SV monitor
28
$
0200
SV1
SET
28
$
200
SV1
Change SV1 to 200 °C.
SET
R/S
The new set value is stored by
pressing the key.
SET
Set value change and registration
The blinking digit indicates which digit can be
set. The blinking digit can be moved by pressing
the key.
However, the changed data is not stored by the
operation of the and keys alone. In order
for the new parameter value to be stored, the
key must be pressed within 1 minute after the
new value is displayed. The new value will then
be saved and the display will move to the next
parameter.
R/S
SET