8. PARAMETER DESCRIPTION
IMR02C15-E4
8-96
Dummy
Function block 30 (F30)
This is the first parameter symbol of Function block 30 (F30).
F30
Output action at STOP mode
Use to select action of Event output or Transmission output when the controller
is set to STOP (control STOP).
Data range Factory set value
0: Both event output and transmission output
(AO) are off.
1: Event output remains unchanged, and
transmission output (AO) is off.
2: Event output is off, and transmission output
(AO) remains unchanged.
3: Both event output and transmission output
(AO) remain unchanged.
0
When the Digital output (DO1 to DO4) and Transmission output are not
provided, this parameter is invalid.
Related parameters
Engineering mode:
• Event 1 type (P. 8-101)
• Event 2 type (P. 8-101)
• Event 3 type (P. 8-101)
• Event 4 type (P. 8-101)
F30.
SS