2. MOUNTING
IMR02C15-E4
2-7
Mounting procedures (Not supplied)
1. Prepare the panel cutout as specified in 2.2 Dimensions.
(Panel thickness: 1 to 10 mm)
2. Insert the instrument through the panel cutout. (Fig. 2.2)
3. Insert the mounting bracket into the mounting groove of
the instrument. (Fig. 2.3)
4. Push the mounting bracket forward until the bracket is
firmly secured to the panel. (Fig. 2.4)
5. Turn only one full revolution after the screw touches the
panel. (Fig. 2.5)
6. The other mounting bracket should be installed the same way described in 3 to 5.
Fig. 2.1
Panel
Mounting
holes
Fig. 2.5
Fig. 2.3
Fig. 2.4
Panel
Fig. 2.2